<?xml version='1.0' encoding='utf-8'?> <oai_dc:dc xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/ http://www.openarchives.org/OAI/2.0/oai_dc.xsd"> <dc:creator>Cayci, H.</dc:creator> <dc:creator>Ayhan, B.</dc:creator> <dc:creator>Kefeli, T.</dc:creator> <dc:date>2018-01-01</dc:date> <dc:description>Existing mobile calibration standard used for on-site calibration of transformer loss measurement systems has been upgraded. Master-slave configuration of programmable power sources is replaced with the external triggering and synchronization method which ensures the system stability below 50 ppm. Resolution in phase-settings between voltage and current generation is now improved about 2-digits down to 1 m degrees. And, measurement results are automatically evaluated with the corrected calibration values of system components.</dc:description> <dc:identifier>https://aperta.ulakbim.gov.trrecord/93435</dc:identifier> <dc:identifier>oai:zenodo.org:93435</dc:identifier> <dc:rights>info:eu-repo/semantics/openAccess</dc:rights> <dc:rights>http://www.opendefinition.org/licenses/cc-by</dc:rights> <dc:title>An Improved Mobile Calibration Standard for Transformer Loss Measurement Systems</dc:title> <dc:type>info:eu-repo/semantics/conferencePaper</dc:type> <dc:type>publication-conferencepaper</dc:type> </oai_dc:dc>