International Comparison of Current Transformer Calibration Systems up to 10 kA at 50 Hz Frequency

  • 1. Czech Tech Univ, Prague, Czech Republic
  • 2. CMI, Brno, Czech Republic
  • 3. VSL, Delft, Netherlands
  • 4. BEV, Villach, Austria
  • 5. BIM, Sofia, Bulgaria
  • 6. DMDM, Belgrade, Serbia
  • 7. GUM, Warsaw, Poland
  • 8. INRIM, Turin, Italy
  • 9. LCOE, Madrid, Spain
  • 10. LNE, Paris, France
  • 11. METAS, Koniz, Switzerland
  • 12. NPL, Teddington, Middx, England
  • 13. PTB, Braunschweig, Germany
  • 14. SP, Gothenburg, Sweden

Description

Current transformers (CTs) are precision devices that scale high currents down to values that can be easily handled by measurement equipment. To support CT applications in revenue metering, a comparison on AC current transformer calibration systems was performed among 15 European national metrology institutes using a precision CT as the travelling device. The first comparison results for the transformation ratios (4, 5, 6, 8, 10) kA/5 A of the travelling CT at nominal burden of 5 VA and 15 VA indicate good agreement between the participating laboratories. The main differences are found for phase displacement, at least partly caused by the instability of the traveling standard.