Two-folded implementation of a 12-pulse TCR with dissimiliar transformers for a ladle furnace: Reactive power compensation and power system redundancy
Description
This paper is devoted to the design and implementation of a 12-pulse Thyristor Controlled Reactor (TCR) system, which constitutes a low-cost solution to the reactive power compensation problem of a ladle furnace in Iskenderun Iron & Steel Plant (ISDEMIR). Design objectives and elimination of 5(th) and 7(th) harmonic current components produced by 6-pulse TCRs are met by connecting two sets of 6 kV, 6 MVAr TCRs to the 34.5 kV ladle furnace bus by the use of two separate converter transformers with delta- and wye-connected secondaries. The effects of dissimilarities between the two sets of 6-pulse TCRs on the harmonic current content of the resulting 12-pulse TCR system are also presented in this paper. Both reactive power compensation and power system redundancy objectives are met by using two separate and dissimilar transformers instead of a single transformer with identical A-and Y-connected secondaries for connection to 6-pulse TCRs, resulting in a two-folded design. One of these transformers is chosen as a sufficiently large unit with two identical A-connected secondaries to supply the ladle furnace in emergency or during maintenance periods of main transformer. In normal operation mode of the resulting ladle furnace power system, the 12-pulse TCR implemented in the project gives quite satisfactory results in reactive power compensation and nearly meets harmonic standards currently used in the country.
Files
bib-c35cbb8a-12d1-47ad-9ed4-f168bac9a240.txt
Files
(358 Bytes)
| Name | Size | Download all |
|---|---|---|
|
md5:22ea4a1783684203b0fe0cdea6b913ce
|
358 Bytes | Preview Download |