Yayınlanmış 1 Ocak 2016 | Sürüm v1
Dergi makalesi Açık

Forced Convective Condensation of R134A Vapor Inside a Vertical Microfin Tube

  • 1. Mersin Univ, Fac Engn, Dept Mech Engn, Yenisehir Mersin, Turkey
  • 2. Istanbul Tech Univ, Fac Mech Engn, Istanbul, Turkey

Açıklama

In this study, condensation of pure refrigerant R134a vapor inside a vertical 18 degrees helical microfin tube was experimentally investigated. Tests were performed at saturation pressure of 5.7-5.9 bar with mass fluxes of 20-100 kg/m(2)s and heat fluxes of 1.7-5.3 kW/m(2). The effects of mass flux and the temperature difference between the refrigerant and tube wall (T) on the heat transfer performance were analyzed throughout experimental data. For experiments in which T is more than 2.5 degrees C, the average condensation Nusselt number showed a tendency to be independent from T. Heat transfer enhancement ratio was found to be 1.59-1.71, which is always higher than the heat transfer area enhancement factor (1.55). Fins always act as a turbulence promoter in the given experimental data range. Finally, the most widely used heat transfer coefficient correlations for condensation inside microfin tubes were analyzed through the experimental data. Best fit was obtained with Yu and Koyama's correlation with an absolute mean deviation of 17% and Kedzierski and Goncalves's correlation with an absolute mean deviation of 19%.

Dosyalar

bib-798ab429-1123-4493-9606-91de07dea822.txt

Dosyalar (153 Bytes)

Ad Boyut Hepisini indir
md5:900661a7efaa61431d838a307eb7fc8d
153 Bytes Ön İzleme İndir