The Development of a Coordinated Anti-Islanding Protection for Collector Systems With Multiple Distributed Generation Units
Creators
- 1. Univ New Brunswick, Dept Elect & Comp Engn, Fredericton, NB E3B 5A3, Canada
- 2. Karadeniz Tech Univ, Dept Elect & Elect Engn, TR-61080 Trabzon, Turkey
- 3. Univ New Brunswick, Dept Elect & Comp Engn, Fredericton, NB E3B2Y1, Canada
Description
This paper presents a coordinated anti-islanding protection for collector systems with multiple distributed generation units (DGUs). The presented anti-islanding protection is established based on processing the d-q-axis components of the instantaneous three phase apparent powers (s(d) and s(q)) determined at the point-of-common-coupling using the wavelet packet transform (WPT). Processing s(d) and s(q) by using WPT allows the extraction of low-and high-frequency sub-band contents. The contents of the high-frequency sub-band are used to detect and distinguish islanding events, and contents of the low-and high-frequency sub-bands are employed to define a coordination index, which is used to identify the islanded DGU(s). The presented anti-islanding protection is implemented for off-line testing using data obtained from a laboratory collector with four different DGUs. Off-line test results demonstrate accurate, fast, and reliable responses to islanding and nonislanding event(s), and accurate identification of islanded DGUs along with negligible sensitivity to levels of power delivery to the collector system.
Files
bib-67ec2625-6780-41e6-8b84-72f6273c78bb.txt
Files
(232 Bytes)
| Name | Size | Download all |
|---|---|---|
|
md5:0ac3ddd49155eb858912e935c216e4c4
|
232 Bytes | Preview Download |