Yayınlanmış 1 Ocak 2007 | Sürüm v1
Konferans bildirisi Açık

Output voltage control of a four-leg inverter based three-phase UPS by means of stationary frame resonant filter banks

  • 1. Middle E Tech Univ, Dept Elect & Elect Engn, TR-06531 Ankara, Turkey

Açıklama

A method for high performance output voltage control of a four-leg inverter (FLI) based three-phase UPS is proposed. Stationary frame resonant filter bank based output voltage control loop, which is complemented by capacitor current feedback based active damping loop, is employed. Utilizing the zero-state partitioning variable, a generalized form of scalar PWM for the FLI is developed and the minimum loss discontinuous PWM method is derived. The controller and modulator design and implementation details for the FLI-UPS are given. Linear and nonlinear loads for balanced and unbalanced load operating conditions are considered. The scalar control and PWM methods are proven by means of theory, simulations, and experiments.

Dosyalar

bib-4b4a89ec-a4dc-45eb-85cf-b75a6f0a9bd8.txt

Dosyalar (272 Bytes)

Ad Boyut Hepisini indir
md5:0cf636144cd077661e4da8669a830eef
272 Bytes Ön İzleme İndir