Published January 1, 2021 | Version v1
Journal article Open

Improvement of the polyurethane spring isolation device for HV post insulators and its evaluation by fragility curves

  • 1. Univ Bristol, Dept Civil Engn, Bristol, Avon, England
  • 2. Istanbul Tech Univ, Fac Civil Engn, TR-34469 Istanbul, Turkey

Description

A novel seismic base isolation system has been developed for high-voltage (HV) porcelain post insulators. The seismic isolation device consists of two steel plates, four polyurethane springs, and a steel rod, which are low-cost components compared to the post insulators. Two alternative designs of the device are experimentally and numerically assessed in this article. A simple and robust numerical model consisting of linear line elements and nonlinear springs was generated, and subsequently validated using the experimental results. Incremental dynamic analyses (IDAs) were then performed to obtain fragility curves. Ten historical earthquake profiles, scaled to intensities between 0.1 and 2.0 g, were then applied to the numerical models. The fragility curves, generated according to the latest version of IEEE-693, demonstrate that the seismic isolation devices are highly effective in diminishing the base moment of the porcelain insulator. It should be noted that relatively large displacements at the top of the pole must be accounted for by ensuring adequate slackness in the flexible conductors.

Files

bib-1e7d2c69-34ca-4564-88d3-148eee950c32.txt

Files (202 Bytes)

Name Size Download all
md5:c08e9a32d924fa5dbb7c91879dc2a01b
202 Bytes Preview Download